Oil-and-gas hot-water

Hot-water boiler

A compact body for the same output

A hot-water boiler on liquid and gaseous fuel with the same output line as the Scotch-type boiler, but in a shorter, more compact body — for where the boiler room is limited in area.

Hot-water boiler
93—4060kW
Output
24
Models
up to 95%
Efficiency
4bar
Pressure
Steel
Build
Design

A compact body for the same output

01

Three flue-gas passes

A fully cylindrical design and turbulators in the flue tubes — combustion efficiency up to 95%.

02

Control panel

Microprocessor-based — it controls both the burner and the pump system from one point.

03

80 mm insulation

A mineral insulation agent on the body and front cover.

04

Pressure up to 10 bar

Standard build is 4 bar, up to 10 bar on request.

05

Service without dismantling

The front covers open — no need to remove the burner.

06

On-site manufacturing

Large sizes are assembled at the customer's site.

Features

  • A fully cylindrical boiler
  • Turbulators in the flue tubes
  • Ribbed aluminium sheet
  • Opening front covers, no burner removal
  • You can walk on the top panel
  • On-site manufacturing option
  • Boiler tube 3.1 per norm 10217-2
  • Compliance with national and international norms
  • A shared service network
Model range · Output, kW
80
100
125
150
175
200
250
300
350
400
450
500
Technical parameters

Technical parameters

The full model range. The table scrolls horizontally.

Range VMEX 80—500

ModelVMEX 80VMEX 100VMEX 125VMEX 150VMEX 175VMEX 200VMEX 250VMEX 300VMEX 350VMEX 400VMEX 450VMEX 500
Output (thous. kcal/h)80100125150175200250300350400450500
Output (kW)93116145174203232290348406464522580
WidthA (mm)771771771894894894947947947111311131113
HeightH (mm)791791791914914914967967967113311331133
Height H1H1 (mm)968968968109110911091114411441144131213121312
LengthL (mm)134914291529152916291629187920542054204021402290
Base lengthL1 (mm)78288298298210821082133214871487148715871732
Tube diameterE (mm)200200200200200200300300300300300300
Tube heightH2 (mm)550550550665665665670670670849849849
Hot-water outlet / inletF (DN)65656565656565658080100100
Water consumption (L)118135138240260251354376357578610670
Dry weight (kg)425460505610660670815885925107011451275
Safety valveS (in)1¼″1¼″1¼″1¼″1¼″1¼″1¼″1¼″1¼″1¼″1½″1½″
Water fill / drainS1 (in)½″½″½″½″½″½″½″½″½″1″1″1″
Condensate drainC (in)½″½″½″½″½″½″½″½″½″1″1″1″
Back pressure (mbar)1.21.31.52.22.32.52.833.85.25.25.7
Working pressure (bar)444444444444

Range VMEX 600—3500

ModelVMEX 600VMEX 700VMEX 800VMEX 900VMEX 1000VMEX 1250VMEX 1500VMEX 1750VMEX 2000VMEX 2500VMEX 3000VMEX 3500
Output (thous. kcal/h)60070080090010001250150017502000250030003500
Output (kW)696812928104411601453174020302320290034804060
WidthA (mm)126912691269146314631463165416541654164817821880
HeightH (mm)130913091309148314831483167416741674168818021900
Height H1H1 (mm)149014901490166416641664185518551855197119852083
LengthL (mm)228724072557254925492754305433543754406050854612
Base lengthL1 (mm)173418341984198419842189248427843184347445153986
Tube diameterE (mm)350350350500500500500500500500500500
Tube heightH2 (mm)945945945107810781078126412641264127913611510
Hot-water outlet / inletF (DN)125125125125125125150150150200200200
Water consumption (L)900932996136813851412208823632731271427312580
Dry weight (kg)148016951780218023602510345038554430494565556900
Safety valveS (in)1½″1½″1½″2″2″2″2½″2½″2½″2½″2½″2½″
Water fill / drainS1 (in)1″1″1″1″1″1″1″1″1″1″1″1″
Condensate drainC (in)1″1″1″1″1″1″1″1″1″1″1″1″
Back pressure (mbar)5.85.965.25.25.85.86.26.76.56.87
Working pressure (bar)444444444444

Output is given in thousands of kcal/h. Dimensions in mm, connections in inches.